Description: Medium voltage cable
Conductor material: bare copper
Conductor construction: stranded, class 2
Insulation: XLPE DIX8
Sheathing material: PVC DMV6
Flame retardant: VDE 0482-332-1-2/IEC 60332-1
Max. temperature at conductor: 90 °C
Max. operating temperature, fixed: +70 °C
Temperature, moved/during instal.: -5 - +70 °C
Bending radius, fixed installation: 15 x DA
Nominal voltage Uo: 6 kV
Nominal voltage U: 10 kV
Test voltage: 21 kV
Max. permitted operating voltage in 3-phase systems: 12 kV
Partial discharge: 2 pC