6-CYKCYDY
For fixed installation indoors and outdoors, in the ground and concrete where is possible mechanical demage risk. The cables are resistant to UV radiation and flame spread.
Product information
									Conductor material:
									bare copper
								
															
									Conductor construction:
									stranded, class 2
								
															
									Insulation:
									PVC
								
															
									Sheathing material:
									PVC
								
															
									Nominal voltage Uo:
									3,6 kV
								
															
									Nominal voltage U:
									6 kV
								
															
									Test voltage:
									12,5 kV
								
															
									Inner sheath:
									PVC
								
															
									Flame retardant:
									ČSN EN 50-265-2-1
								
															
									Separator:
									semiconductive tape
								
															
									Max. operating temperature:
									70 °C
								
															
									Min. operating temperature:
									-35 °C
								
															
									Max. short circuit temperature:
									160 °C
								
															
									Armouring:
									galvanized steel wires
								
															
									Operating	core	temperature:
									70 °C
								